APC Switched Rack Power Distribution Unit (PDU) Guida Utente Pagina 44

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 43
35Metered-by-Outlet With Switching Rack PDU User Guide
humLow
Access: Administrator, Device User
Description: Set or view the low humidity threshold as a percent of the relative humidity.
Example 1: To view the low humidity threshold, type:
apc> humLow
E000: Success
10 %RH
Example 2: To set the low humidity threshold, type:
apc> humLow 12
E000: Success
Example 3: To view the low humidity threshold on guest Rack PDU 3, type:
apc> humLow 3:
E000: Success
10 %RH
humMin
Access: Administrator, Device User
Description: Set or view the minimum humidity threshold as a percent of the relative humidity.
Example 1: To view the minimum humidity threshold, type:
apc> humMin
E000: Success
6 %RH
Example 2: To set the minimum humidity threshold, type:
apc> humMin 8
E000: Success
Example 3: To set the minimum humidity threshold on guest Rack PDU 3 to 18% RH, type:
apc> humMin 3:18
E000: Success
humReading
Access: Administrator, Device User, Outlet User
Description: View the humidity value from the sensor.
Example 1: To view the humidity value, type:
apc> humReading
E000: Success
25 %RH
Example 2: To view the humidity value on guest Rack PDU 2, type:
apc> humReading 2:
E000: Success
48 %RH
Vedere la pagina 43
1 2 ... 39 40 41 42 43 44 45 46 47 48 49 ... 129 130

Commenti su questo manuale

Nessun commento