35User Guide InfraStruxure 150kVA Power Distribution Unit
sysThrMnV
Access: Administrator, Device
Description: Configure the minimum voltage (L-N) alarm threshold and enable a corresponding critical
alarm. The minus sign is implied, not expressed. Parameters: [<fraction>] [<enable|disable>]
Fraction = percent below device nominal voltage.
Example:
apc> sysThrMnV
1. -20%,Disable
apc> sysThrMnV Enable
1. -20%,Enable
apc> sysThrMnV
1. -20%,Enable
sysThrMxI
Access: Administrator, Device
Description: Configure the maximum current alarm threshold and enable a corresponding critical
alarm. Parameters: [<fraction>] [<enable|disable>]
Fraction = percent of rated current.
Example:
apc> sysThrMxI
1. 0%,Disable
apc> sysThrMxI 90 Enable
1. 90%,Enable
apc> sysThrMxI
1. 90%,Enable
sysThrHiI
Access: Administrator, Device
Description: Configure the high current alarm threshold and enable a corresponding warning alarm.
Parameters: [<fraction>] [<enable|disable>]
Fraction = percent of rated current.
Example:
apc> sysThrHiI
1. 0%,Disable
apc> sysThrHiI 80 Enable
1. 80%,Enable
apc> sysThrHiI
1. 80%,Enable