59User Guide InfraStruxure 150kVA Power Distribution Unit
Parameters: [<relay> <enable|disable>]
relay = output relay to be triggered(normally 1|2|3|4).
Example:
apc> orSysFreq
1. System Frequency,1,disable,2,disable,3,disable,4,disable
apc> orSysFreq 4 enable
1. Subfeed 1 Breaker Position,1,disable,2,disable,3,disable,4,enable
orICxxxxx
Access: Administrator, Device
Description: This category of alarm mapping commands associates an input contact alarm with the
output relay/relays designated in the parameters. With no parameter, display the current associated
relays.
Subfeed alarm association commands:
orIC1Alrm
orIC2Alrm
orIC3Alrm
orIC4Alrm
Parameters: [<relay> <enable|disable>]
relay = output relay to be triggered(normally 1|2|3|4).
Example:
apc> orIC2Alrm
1. Input Contact 2,1,disable,2,disable,3,disable,4,disable
apc> orIC2Alrm 4 enable
1. Input Contact 2,1,disable,2,disable,3,disable,4,enable