APC PD40G6FK1-M Manuale delle Istruzioni Pagina 11

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 16
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 10
7InfraStruXure Power Distribution Unit 40kW Instructions for Electricians
Install a circuit breaker
Warning: When you connect the InfraStruXure PDU to utility power, you must install a
circuit breaker to protect the PDU against over-current.
Determine the amperage of the circuit breaker that you need to install:
Route the input conductors to the Main Input switch
For overhead wiring, run the input conductors directly to the Main Input switch.
For wiring under a raised floor, run the input conductors through the wireway (
)
within the PDU to the Main Input switch.
Input Voltage Circuit Breaker Amperage
208V 175A
480V 80A
600V 60A
Vedere la pagina 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16

Commenti su questo manuale

Nessun commento