3InfraStruXure Power Distribution Unit 40kW Instructions for Electricians
Torque specs and tools required
Before connecting to the terminals, verify the torque specs below by checking the specifications on the Main
Input switch.
Terminal Torque Tools
L1, L2, L3 150 in-lb 6-mm Allen wrench
N
125 in-lb 13-mm socket wrench
G, G EC 4 – 6 AW G : 45 i n -l b
8 AWG: 40 in-lb
Slotted screwdriver