42 Implementing UPS Configurations with Microsoft Cluster Server
Figure 36. Single UPS Run Command File Low Battery Condition
9. Now select Low Battery Condition in the Event Actions window.
a. Check Run Command File the checkbox and click Options.
b. In the pop-up window, insert the following in the Command File field:
“C:\UPS_CMD\UPS.CMD” SingleUPSOnBattery >> C:\UPS_CMD\LOG.TXT
c. Set the Wait value to 0 seconds. A low battery condition means that the
UPS can only supply the systems for a short period and immediate actions
must take place. This wait time forces immediate execution of the
command file when a low battery condition occurs. Click the OK button to
apply your choices.
Vedere la pagina 49