50 Implementing UPS Configurations with Microsoft Cluster Server
Figure 49. Single UPS Run Command File Low Battery Condition
7. In the Event Actions window, select Low Battery Condition.
a. Select the Run Command File checkbox and click Options.
b. In the pop-up window, enter the following in the Command File field:
“C:\UPS_CMD\UPS.CMD” SingleUPSOnBattery >> C:\UPS_CMD\LOG.TXT
c. Set Wait to 0 seconds. A low battery condition means that the UPS can
supply the systems for a short period only and immediate actions must take
place. This wait time forces immediate execution of the command file when
a low battery condition occurs. Click the OK button to apply your choices.
Figure 50. Single UPS Event Actions