USER’S GUIDE
NetBotz Rack Monitor 200
103
7. Type open and the Main Module IP address, then press ENTER. If the port
setting for the FTP Server has changed from its default of 21, use the non-
default port number you obtained in step 2 in the FTP command.
For Windows FTP clients, separate a non-default port number from the IP
address by a space. For example:
ftp> open 150.250.6.10 21000
Some FTP clients require a colon instead of a space before the non-default port
number.
8. Log on to the NetBotz Rack Monitor 200 as Administrator; apc is the default
user name and password.
9. Upgrade the AOS; the file name you enter must match the name of the binary
AOS file you extracted. In the example below, xs were substituted for version
numbers.
ftp> bin
ftp> put apc_hwxx_aos_xxx.bin
10. When FTP confirms the transfer, type quit to close the session.
11. After 20 seconds, repeat step 6 through step 8.
12. Upgrade the application file; the file name you enter must match the name of
the binary application file you extracted. In the example below, x’s were
substituted for version numbers.
ftp> bin
ftp> put apc_hwxx_nb200_xxx.bin
13. When FTP confirms the transfer, type quit to close the session.
For a successful firmware upgrade, you must first transfer the AOS file and then
transfer the application file.