USER’S GUIDE
NetBotz Rack Monitor 200
75
Syslog Test and Format Example (Logs>Syslog>test). Send a test message to
the Syslog servers configured through the servers option.
1. Select a severity to assign to the test message.
2. Define the test message, according to the required message fields:
–The priority (PRI): The Syslog priority assigned to the message’s event, and the
facility code of messages sent by the Main Module.
–The Header: A time stamp and the IP address of the Main Module.
–The message (MSG) part:
•The TAG field, followed by a colon and space, identifies the event type.
•The CONTENT field is the event text, followed (optionally) by a space and the
event code.
For example, APC: Test Syslog is valid.