USER’S GUIDE
NetBotz Rack Monitor 200
38
To configure all sensors or a defined group: Follow this procedure to mass
configure all sensors or a defined group of sensors. You can mass configure
temperature and humidity thresholds, rate of change settings, the alarm generation
setting, and the name and location. When mass-configuring Name and Location
fields, you can use wildcards so the system creates unique names and locations based
on automatically detected data about the module to which the sensor is connected.
1. Use filter settings to display the group of sensors to mass configure. (For
information on setting filters, see Tables.)
2. Click Mass Configuration. Make selections, then click Next.
Humidity Threshold
Hysteresis
The difference between the humidity threshold violation and the
clearing point. Increasing this value prevents frequent alarms if
humidity wavers slightly above and below the threshold before
corrective actions restore the humidity to the clearing point.
Rate of Change Settings
Short-term Increasing
Temperature Rate of
Change
Set the maximum short-term increase in temperature that you want
your system to allow. An alarm will occur if the temperature
increases at a rate that is greater than the rate you have set.
Short-term Decreasing
Temperature Rate of
Change
Set the maximum short-term decrease in temperature that you want
your system to allow. An alarm will occur if the temperature
decreases at a rate that is greater than the rate you have set.
Long-term Increasing
Temperature Rate of
Change
Set the maximum long-term increase in temperature that you want
your system to allow. An alarm will occur if the temperature
increases at a rate that is greater than the rate you have set.
Long-term Decreasing
Temperature Rate of
Change
Set the maximum long-term decrease in temperature that you want
your system to allow. An alarm will occur if the temperature
decreases at a rate that is greater than the rate you have set.