USER’S GUIDE
NetBotz Rack Monitor 200
80
The graph legend shows the color of the graph line for each selected data item. If the
data items do not have the same unit of measurement, the units are displayed in the
legend. If the data items do have the same units, the unit is displayed on the left side of
the graph.
Move the mouse pointer over any horizontal line to view the date, time, and Y-axis
value for that data record.
Use the Zoom menu to increase or decrease the magnification of the graph. The blue
bar at the top left corner of the graph changes size to indicate the number of total data
records being displayed and the relative location of the displayed data records. To
re-center the graph, click any point on the graph or the blue bar.
Setting the data collection interval (Logs>Data>interval). Define how frequently
data is sampled and stored in the data log and view the calculation of how many days
of data the log can store, based on the interval you selected. When the log is full, the
older entries are deleted. To avoid automatic deletion of older data, enable and
configure data log rotation, described in the next section.
Configuring data log rotation (Logs>Data>rotation). Set up a password-protected
data log repository on a specified FTP server. Enabling rotation causes the contents of
the data log to be appended to the file you specify by name and location. Updates to
this file occur at the upload interval you specify.
Parameter Description
Data Log Rotation Enable or disable (the default) data log rotation.
FTP Server Address The location of the FTP server where the data repository file is stored.
User Name The user name required to send data to the repository file. This user must
also be configured to have read and write access to the data repository
file and the directory (folder) in which it is stored.
Password The password required to send data to the repository file.
File Path The path to the repository file.