APC NetBotz 200 Guida Utente Pagina 34

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 125
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 33
®
USER’S GUIDE
NetBotz Rack Monitor 200
28
Device Connection Procedure
Universal Sensor Port
or Beacon port
1. Make sure the device cable connection is secure and that the
cable has not been damaged.
2. Replace the device with a known good device of the same
type. Did an alarm appear for the known good device?
No. The device was bad.
Yes. There is a problem with the Main Module or Expansion
Module to which the device is connected.
A-Link port 1. Make sure cables are correctly and securely connected to the
in and out ports of all devices on the A-Link bus.
2. Make sure A-Link terminators are securely installed in unused
A-Link ports.
3. Make sure the maximum combined length of all A-Link cables
does not exceed 1000 m (3,280 ft).
N
OTE:When one remote sensor or Expansion Module has a
problem that causes a Device Disconnected alarm, all devices
cascaded from the output port of the device will also report a
Device Disconnected alarm.
4. If more than one Device Disconnected alarm exists for
devices that connect to A-Link ports, starting from the Main
Module, identify the first device on the A-Link chain with the
alarm.
5. Make sure the cable to the device input port has not been
damaged.
6. Disconnect cables from one or both A-Link ports on the Main
Module (Rack Monitor 200), as applicable. Did the alarm go
away?
No. A hardware problem exists with the Rack Monitor 200.
Yes. Re-connect cables to the A-Link ports and continue this
procedure.
7. Replace the device with a known good device. Did the alarm
go away?
No. Replace the cable to the device input connector.
Yes. The device that was removed was bad.
Vedere la pagina 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 124 125

Commenti su questo manuale

Nessun commento